@@ -0,0 +1,349 @@
|
|
|
+name: Combo heat pump
|
|
|
+products:
|
|
|
+ - id: kjf6gjn1kaawfyjk
|
|
|
+ manufacturer: Chiltrix
|
|
|
+ model: CX50
|
|
|
+
|
|
|
+entities:
|
|
|
+ # PRIMARY HVAC (CLIMATE)
|
|
|
+ - entity: climate
|
|
|
+ name: Air
|
|
|
+ dps:
|
|
|
+ # Power control
|
|
|
+ - id: 126
|
|
|
+ type: boolean
|
|
|
+ name: hvac_mode
|
|
|
+ mapping:
|
|
|
+ - dps_val: false
|
|
|
+ value: "off"
|
|
|
+ available: water_off
|
|
|
+ - dps_val: true
|
|
|
+ constraint: mode
|
|
|
+ conditions:
|
|
|
+ - dps_val: "cool"
|
|
|
+ value: cool
|
|
|
+ available: water_off
|
|
|
+ - dps_val: "heat"
|
|
|
+ value: heat
|
|
|
+ available: water_off
|
|
|
+ - dps_val: "dhw"
|
|
|
+ value: "off"
|
|
|
+ available: water_on
|
|
|
+ - dps_val: "cool_dhw"
|
|
|
+ value: cool
|
|
|
+ available: water_on
|
|
|
+ - dps_val: "heat_dhw"
|
|
|
+ value: heat
|
|
|
+ available: water_on
|
|
|
+
|
|
|
+ # Mode enum
|
|
|
+ - id: 130
|
|
|
+ type: string
|
|
|
+ name: mode
|
|
|
+ hidden: true
|
|
|
+
|
|
|
+ # Helper: water heating inactive
|
|
|
+ - id: 130
|
|
|
+ type: string
|
|
|
+ name: water_off
|
|
|
+ hidden: true
|
|
|
+ mapping:
|
|
|
+ - dps_val: "cool"
|
|
|
+ value: true
|
|
|
+ - dps_val: "heat"
|
|
|
+ value: true
|
|
|
+ - value: false
|
|
|
+
|
|
|
+ # Helper: water heating active
|
|
|
+ - id: 130
|
|
|
+ type: string
|
|
|
+ name: water_on
|
|
|
+ hidden: true
|
|
|
+ mapping:
|
|
|
+ - dps_val: "dhw"
|
|
|
+ value: true
|
|
|
+ - dps_val: "cool_dhw"
|
|
|
+ value: true
|
|
|
+ - dps_val: "heat_dhw"
|
|
|
+ value: true
|
|
|
+ - value: false
|
|
|
+
|
|
|
+ # Target temperature (return water setpoint for HVAC)
|
|
|
+ - id: 101
|
|
|
+ type: integer
|
|
|
+ name: temperature
|
|
|
+ unit: C
|
|
|
+ range:
|
|
|
+ min: 0
|
|
|
+ max: 80
|
|
|
+
|
|
|
+ # Current temperature (return water as proxy)
|
|
|
+ - id: 111
|
|
|
+ type: integer
|
|
|
+ name: current_temperature
|
|
|
+
|
|
|
+ # DHW WATER HEATER
|
|
|
+ - entity: water_heater
|
|
|
+ name: DHW
|
|
|
+ dps:
|
|
|
+ # Power & operation mode combined
|
|
|
+ - id: 126
|
|
|
+ type: boolean
|
|
|
+ name: operation_mode
|
|
|
+ mapping:
|
|
|
+ - dps_val: false
|
|
|
+ value: "off"
|
|
|
+ available: air_off
|
|
|
+ - dps_val: true
|
|
|
+ constraint: mode
|
|
|
+ conditions:
|
|
|
+ - dps_val: "dhw"
|
|
|
+ value: heat_pump
|
|
|
+ available: air_off
|
|
|
+ - dps_val: "cool"
|
|
|
+ value: "off"
|
|
|
+ available: air_cool
|
|
|
+ - dps_val: "cool_dhw"
|
|
|
+ value: heat_pump
|
|
|
+ available: air_cool
|
|
|
+ - dps_val: "heat"
|
|
|
+ value: "off"
|
|
|
+ available: air_heat
|
|
|
+ - dps_val: "heat_dhw"
|
|
|
+ value: heat_pump
|
|
|
+ available: air_heat
|
|
|
+
|
|
|
+ # Mode enum (hidden)
|
|
|
+ - id: 130
|
|
|
+ type: string
|
|
|
+ name: mode
|
|
|
+ hidden: true
|
|
|
+
|
|
|
+ # Helper: air off (dhw only)
|
|
|
+ - id: 130
|
|
|
+ type: string
|
|
|
+ name: air_off
|
|
|
+ hidden: true
|
|
|
+ mapping:
|
|
|
+ - dps_val: "dhw"
|
|
|
+ value: true
|
|
|
+ - value: false
|
|
|
+
|
|
|
+ # Helper: air cooling active
|
|
|
+ - id: 130
|
|
|
+ type: string
|
|
|
+ name: air_cool
|
|
|
+ hidden: true
|
|
|
+ mapping:
|
|
|
+ - dps_val: "cool"
|
|
|
+ value: true
|
|
|
+ - dps_val: "cool_dhw"
|
|
|
+ value: true
|
|
|
+ - value: false
|
|
|
+
|
|
|
+ # Helper: air heating active
|
|
|
+ - id: 130
|
|
|
+ type: string
|
|
|
+ name: air_heat
|
|
|
+ hidden: true
|
|
|
+ mapping:
|
|
|
+ - dps_val: "heat"
|
|
|
+ value: true
|
|
|
+ - dps_val: "heat_dhw"
|
|
|
+ value: true
|
|
|
+ - value: false
|
|
|
+
|
|
|
+ # DHW setpoint
|
|
|
+ - id: 102
|
|
|
+ type: integer
|
|
|
+ name: temperature
|
|
|
+ unit: C
|
|
|
+ range:
|
|
|
+ min: 10
|
|
|
+ max: 70
|
|
|
+
|
|
|
+ # Current DHW temperature
|
|
|
+ - id: 113
|
|
|
+ type: integer
|
|
|
+ name: current_temperature
|
|
|
+
|
|
|
+ # EXTRA CONFIG NUMBERS
|
|
|
+ - entity: number
|
|
|
+ name: Minimum water flow
|
|
|
+ category: config
|
|
|
+ class: volume_flow_rate
|
|
|
+ dps:
|
|
|
+ - id: 103
|
|
|
+ type: integer
|
|
|
+ name: value
|
|
|
+ unit: L/min
|
|
|
+ range:
|
|
|
+ min: 0
|
|
|
+ max: 60
|
|
|
+
|
|
|
+ # TEMPERATURE & FLOW SENSORS
|
|
|
+ - entity: sensor
|
|
|
+ name: Output temperature
|
|
|
+ class: temperature
|
|
|
+ category: diagnostic
|
|
|
+ icon: "mdi:thermometer-chevron-down"
|
|
|
+ dps:
|
|
|
+ - id: 112
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: °C
|
|
|
+ class: measurement
|
|
|
+ mapping:
|
|
|
+ - scale: 10
|
|
|
+
|
|
|
+ - entity: sensor
|
|
|
+ name: Air conditioning water flow
|
|
|
+ category: diagnostic
|
|
|
+ class: volume_flow_rate
|
|
|
+ dps:
|
|
|
+ - id: 114
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: L/min
|
|
|
+ class: measurement
|
|
|
+
|
|
|
+ - entity: sensor
|
|
|
+ name: Compressor temperature
|
|
|
+ class: temperature
|
|
|
+ category: diagnostic
|
|
|
+ icon: "mdi:fire"
|
|
|
+ dps:
|
|
|
+ - id: 115
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: °C
|
|
|
+ class: measurement
|
|
|
+
|
|
|
+ - entity: sensor
|
|
|
+ name: Coil temperature
|
|
|
+ class: temperature
|
|
|
+ category: diagnostic
|
|
|
+ icon: "mdi:pipe"
|
|
|
+ dps:
|
|
|
+ - id: 116
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: °C
|
|
|
+ class: measurement
|
|
|
+
|
|
|
+ - entity: sensor
|
|
|
+ name: Ambient temperature
|
|
|
+ class: temperature
|
|
|
+ category: diagnostic
|
|
|
+ icon: "mdi:thermometer-lines"
|
|
|
+ dps:
|
|
|
+ - id: 117
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: °C
|
|
|
+ class: measurement
|
|
|
+
|
|
|
+ - entity: sensor
|
|
|
+ name: Compressor return temperature
|
|
|
+ class: temperature
|
|
|
+ category: diagnostic
|
|
|
+ icon: "mdi:fan"
|
|
|
+ dps:
|
|
|
+ - id: 118
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: °C
|
|
|
+ class: measurement
|
|
|
+
|
|
|
+ - entity: sensor
|
|
|
+ name: Exchange plate temperature
|
|
|
+ class: temperature
|
|
|
+ category: diagnostic
|
|
|
+ icon: "mdi:pipe-wrench"
|
|
|
+ dps:
|
|
|
+ - id: 119
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: °C
|
|
|
+ class: measurement
|
|
|
+
|
|
|
+ # ELECTRICAL / SPEED
|
|
|
+ - entity: sensor
|
|
|
+ name: Compressor frequency
|
|
|
+ class: frequency
|
|
|
+ category: diagnostic
|
|
|
+ icon: "mdi:engine"
|
|
|
+ dps:
|
|
|
+ - id: 106
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: Hz
|
|
|
+ class: measurement
|
|
|
+
|
|
|
+ - entity: sensor
|
|
|
+ name: Fan speed
|
|
|
+ category: diagnostic
|
|
|
+ icon: "mdi:fan-auto"
|
|
|
+ dps:
|
|
|
+ - id: 107
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: rpm
|
|
|
+ class: measurement
|
|
|
+
|
|
|
+ - entity: sensor
|
|
|
+ class: current
|
|
|
+ category: diagnostic
|
|
|
+ dps:
|
|
|
+ - id: 108
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+ unit: A
|
|
|
+ class: measurement
|
|
|
+ mapping:
|
|
|
+ - scale: 10
|
|
|
+
|
|
|
+ # RAW STATUS WORD
|
|
|
+ - entity: sensor
|
|
|
+ name: Status bits
|
|
|
+ category: diagnostic
|
|
|
+ icon: "mdi:information-outline"
|
|
|
+ hidden: true
|
|
|
+ dps:
|
|
|
+ - id: 120
|
|
|
+ type: integer
|
|
|
+ name: sensor
|
|
|
+
|
|
|
+ # FAULT STATUS (BINARY_SENSOR)
|
|
|
+ - entity: binary_sensor
|
|
|
+ class: problem
|
|
|
+ category: diagnostic
|
|
|
+ dps:
|
|
|
+ # Main fault detection from group 1
|
|
|
+ - id: 104
|
|
|
+ type: string
|
|
|
+ name: sensor
|
|
|
+ mapping:
|
|
|
+ - dps_val: "eorr0"
|
|
|
+ value_redirect: fault_group_2
|
|
|
+ - value: true
|
|
|
+
|
|
|
+ # Fault code 1 as attribute
|
|
|
+ - id: 104
|
|
|
+ type: string
|
|
|
+ name: fault_code
|
|
|
+
|
|
|
+ # Fallback to group 2
|
|
|
+ - id: 105
|
|
|
+ type: string
|
|
|
+ name: fault_group_2
|
|
|
+ hidden: true
|
|
|
+ mapping:
|
|
|
+ - dps_val: "eorr0"
|
|
|
+ value: false
|
|
|
+ - value: true
|
|
|
+
|
|
|
+ # Fault code 2 as attribute
|
|
|
+ - id: 105
|
|
|
+ type: string
|
|
|
+ name: fault_code_2
|